title: "IEEE 1366 explained: SAIDI, SAIFI and reliability | Quantlix"
description: "IEEE 1366 defines the distribution reliability indices utilities report, such as SAIDI, SAIFI and CAIDI, and the major event day method. See how they are calculated."
canonical: "https://quantlix.com/en/standards/ieee-1366/"
last-updated: 2026-11-16
---

Source: https://quantlix.com/en/standards/ieee-1366/
Language: en
Description: IEEE 1366 defines the distribution reliability indices utilities report, such as SAIDI, SAIFI and CAIDI, and the major event day method. See how they are calculated.

**IEEE 1366** [Energy and grid systems](https://quantlix.com/en/standards/#grid)

# IEEE 1366: distribution reliability indices such as SAIDI and SAIFI

IEEE 1366 is the IEEE guide that defines distribution reliability indices such as SAIDI, SAIFI, CAIDI and MAIFI, and the major event day method utilities use to separate extreme days from normal performance.

[Discuss your project](https://quantlix.com/en/contact/) [Read the key points](https://quantlix.com/en/standards/ieee-1366/#standard-overview)

## At a glance

**Full name**

IEEE Guide for Electric Power Distribution Reliability Indices

**Published by**

IEEE Standards Association, Power and Energy Society (Transmission and Distribution Committee)

**Type**

Guide (IEEE standard)

**Current version**

IEEE 1366-2022, approved 21 September 2022 and published 22 November 2022; supersedes 1366-2012. Revision project P1366 approved 4 November 2025

**Applies to**

Distribution utilities, regulators and analysts measuring reliability for whole systems, substations, circuits and defined regions

**Last reviewed**

November 16, 2026 (2026-11-16)

## In plain terms

### Key points

- SAIFI measures how often the average customer loses power, and SAIDI measures how long those interruptions last in total.
- CAIDI, the average restoration time, equals SAIDI divided by SAIFI; MAIFI tracks momentary interruptions.
- The 2.5 beta method sets a major event day threshold from five years of daily SAIDI values.
- IEEE 1366-2022 is current, and a project approved in November 2025 is revising it as a recommended practice.
- The guide defines the indices, while each regulator decides which ones to report and which events to exclude.

### What is IEEE 1366?

IEEE 1366 is **the IEEE guide that defines how to measure the reliability of electricity distribution**. It gives utilities, regulators and analysts a shared set of indices, such as SAIDI and SAIFI, and the factors that affect how they are calculated, so reliability can be compared over time and between systems.

Without common definitions, utilities counted interruptions in different ways, which made one company’s figures hard to compare with another’s, or even with its own earlier years. Agreeing on what an interruption is, who was affected and how long it lasted turns outage records into numbers people can trust and discuss.

### What IEEE 1366 covers

- **Sustained interruption indices.** SAIFI (System Average Interruption Frequency Index) and SAIDI (System Average Interruption Duration Index) show how often and for how long the average customer is without power, counting interruptions longer than five minutes.
- **Customer-based indices.** CAIDI (Customer Average Interruption Duration Index) gives the average restoration time and equals SAIDI divided by SAIFI, and further indices focus on the customers who were actually interrupted.
- **Momentary interruptions.** MAIFI (Momentary Average Interruption Frequency Index) tracks very short interruptions, such as those caused when reclosers clear temporary faults.
- **Major event days.** A statistical method that separates days of extreme impact from normal operation, so each can be studied on its own terms.
- **Definitions and scope.** Terms such as interruption, customers served and reporting period, with indices for whole systems, substations, circuits and defined regions.

### How the major event day method works

A single severe storm can dominate a year of reliability figures and hide real trends in everyday performance. **IEEE 1366 handles this with the 2.5 beta method.** It collects five years of daily SAIDI values, takes the natural logarithm of each, and finds their average (alpha) and standard deviation (beta). The threshold, TMED, is e raised to the power of alpha plus 2.5 beta, and any day in the next reporting period whose SAIDI exceeds it is a major event day.

Major event days are not deleted. They are reported separately, so you can show performance with and without them. In the United States, Form EIA-861 asks utilities that use the IEEE method for SAIDI and SAIFI both with and without major event days. Regulators decide which figures count toward their own targets.

### How it shows up in software projects

- **Clean outage records.** Every interruption needs a start, a restoration time and the number of customers affected, including step restorations where customers come back in stages.
- **Connectivity to customers.** Accurate customer counts depend on a reliable link from devices to transformers to service points, often drawn from the GIS and a network model based on [IEC 61968-11](https://quantlix.com/en/standards/iec-61968-11/).
- **Configurable rules.** The five-minute boundary, event exclusions and the major event day threshold are parameters tied to a recorded edition and regulator rule set, not hard-coded constants.
- **Traceable results.** Each published index traces back to the events behind it, so analysts and regulators can check the numbers.
- **Trend and cause analysis.** Separating major event days lets [data analytics](https://quantlix.com/en/services/data-analytics/) focus on recurring causes, such as vegetation, equipment failures or particular circuits.

### How we work with IEEE 1366

We build reliability reporting from the source data up: pipelines that pull outage and customer data from outage management, GIS and customer systems, calculation engines for the indices and major event days, and dashboards that show performance by circuit, region and cause. Dr. Abdel-Hadi Hor, who leads our Utilities and Infrastructure practice, has worked for over 23 years with the outage and distribution management systems where these numbers start; read his [profile](https://quantlix.com/en/about/leadership/abdel-hadi-hor/).

The indices you file are your organization’s figures, prepared under your regulator’s rules and approved by your own teams. Our role is to make the calculation transparent and repeatable. See how this connects with our wider work in [energy and utilities](https://quantlix.com/en/industries/energy-and-utilities/).

## Where it applies

Industries where this standard often shapes the work.

- ### [Energy & Utilities](https://quantlix.com/en/industries/energy-and-utilities/)

  Renewable energy, smart grids and energy storage systems

## Related standards

[All standards](https://quantlix.com/en/standards/)

- IEC 61968-11

  ### [CIM extensions for distribution](https://quantlix.com/en/standards/iec-61968-11/)

  IEC 61968-11 is the international standard that extends the Common Information Model (CIM) to electricity distribution, so GIS, asset, outage and metering systems can describe the same network in the same way.
- IEC 61970-301

  ### [The CIM base for power systems](https://quantlix.com/en/standards/iec-61970-301/)

  IEC 61970-301 is the international standard that defines the base of the Common Information Model (CIM), a shared description of power system equipment, connectivity and measurements used across grid software.
- ISO 55001

  ### [Asset management system requirements](https://quantlix.com/en/standards/iso-55001/)

  ISO 55001 is the international standard that sets requirements for an organization's asset management system, so decisions about assets deliver value across their whole life.

## Services that support this work

The services we usually bring to projects that involve this standard.

[View all services](https://quantlix.com/en/services/)

### [Data analytics](https://quantlix.com/en/services/data-analytics/)

Quantlix builds analytics pipelines and business intelligence tools that turn operational data into defined metrics, useful reports and decision support.

### [Enterprise applications](https://quantlix.com/en/services/enterprise-applications/)

Quantlix designs and builds enterprise applications for internal workflows, business rules and system integration, with clear access controls and maintainable architecture.

### [Artificial intelligence](https://quantlix.com/en/services/artificial-intelligence/)

Industrial AI for inspection, maintenance and operational decision support. Quantlix scopes data, integration, evaluation and human review around one workflow.

## Questions, answered

What teams usually ask us about this standard.

**What is the difference between SAIDI and SAIFI?**

SAIFI is the average number of sustained interruptions per customer served over a period. SAIDI is the average total interruption duration per customer served, usually in minutes. One measures frequency and the other duration.

**What counts as a sustained interruption?**

Under IEEE 1366, an interruption lasting longer than five minutes is sustained, and shorter ones are momentary and tracked with indices such as MAIFI. Utilities that follow other methods may use different thresholds, so check the rules that apply to you.

**How is a major event day calculated?**

The 2.5 beta method takes five years of daily SAIDI values, finds the average (alpha) and standard deviation (beta) of their natural logarithms, and sets the threshold at e raised to alpha plus 2.5 beta. Days in the next reporting period with daily SAIDI above that threshold are major event days.

**What is the latest version of IEEE 1366?**

IEEE 1366-2022, published on 22 November 2022, which superseded the 2012 edition. On 4 November 2025 the IEEE SA Standards Board approved project P1366 to revise it as a recommended practice.

**Is IEEE 1366 mandatory?**

IEEE does not make it mandatory, since it is a guide. In the United States, Form EIA-861 asks utilities whether they calculate SAIDI and SAIFI by the IEEE method, and state regulators set their own reporting rules, which may refer to it.

## Official sources

Read the official text before relying on any detail. What applies to you depends on your role, your location and the version in force.

- [IEEE 1366-2022 on IEEE SA](https://standards.ieee.org/standard/1366-2022.html)
- [Form EIA-861 frequently asked questions (EIA)](https://www.eia.gov/survey/form/eia_861/faqs.php)
- [IEEE SA Standards Board approvals, 4 November 2025](https://standards.ieee.org/about/sasb/sba/04nov2025/)

These guides explain each standard in plain terms. They are not legal advice, and they do not state that any product or organization conforms to a standard.

## Planning software around this standard?

Tell us which systems are involved and what you need to show. We will help you build the requirements in from the start.