**DNP3** [Energy and grid systems](https://quantlix.com/en/standards/#grid)

# DNP3: the SCADA protocol for utility field devices

DNP3 is the Distributed Network Protocol, standardized as IEEE 1815, that SCADA masters use to poll and control RTUs and IEDs in electric, water and other utilities, with event reporting and time-stamped data.

[Discuss your project](https://quantlix.com/en/contact/) [Read the key points](https://quantlix.com/en/standards/dnp3/#standard-overview)

## At a glance

**Full name**

IEEE Standard for Electric Power Systems Communications, Distributed Network Protocol (DNP3)

**Published by**

IEEE Standards Association (IEEE 1815); the protocol is owned and maintained by the DNP Users Group

**Type**

Communication protocol (IEEE standard)

**Current version**

IEEE 1815-2012, published 10 October 2012; Inactive-Reserved since 30 March 2023, with revision project P1815 active

**Applies to**

Utilities and vendors connecting SCADA masters with substation computers, RTUs and IEDs, mainly in electric power and also in water and oil and gas

**Last reviewed**

November 16, 2026 (2026-11-16)

## In plain terms

### Key points

- DNP3 links masters in control centers to outstations in the field, using polling, event reporting and unsolicited responses.
- IEEE 1815-2012 is the latest edition. IEEE lists it as Inactive-Reserved since March 2023 while the P1815 revision continues.
- The DNP Users Group owns the protocol, publishes test procedures and posts conformance certificates for tested devices.
- IEEE 1815.2-2025, published in February 2026, adds a DNP3 profile for distributed energy resources.
- Secure Authentication is optional, so each link should record whether it is used and what protects the network around it.

### What is DNP3?

DNP3, the Distributed Network Protocol, is **the SCADA protocol standardized as IEEE 1815** that lets control center masters exchange data with field devices. Harris Distributed Automation Products developed it, and in November 1993 ownership passed to the DNP Users Group, a body of utilities and vendors that still maintains it. IEEE first adopted it as IEEE Std 1815 in 2010.

It was built for the realities of utility networks: many remote sites, slow or shared links and a need to know exactly when something happened. The DNP Users Group calls it the most widely used protocol for electric transmission and distribution communications, and it also serves water, transportation and [oil and gas](https://quantlix.com/en/industries/oil-and-gas/) operations.

### What DNP3 covers

- **Roles.** A master in the control center talks to outstations in the field, such as RTUs, IEDs and substation computers.
- **Data types.** Binary inputs, analog inputs, counters and output points, each held as a current value in the outstation database.
- **Events and classes.** Changes, such as a binary input switching state or an analog value moving past its deadband, become time-stamped events sorted into three event classes.
- **Reporting modes.** Masters poll for events often and for static data occasionally as an integrity check, and outstations that support it can send unsolicited responses when something changes.
- **Subset levels and device profiles.** Subset levels let a simple feeder device and a full-featured system implement different amounts of the protocol, and a device profile documents what each product supports.

### Status, profiles and security

**The current edition is IEEE 1815-2012**, published on 10 October 2012 and superseding the 2010 edition. IEEE has listed it as Inactive-Reserved since 30 March 2023, and revision project P1815 is active, so cite the 2012 edition with that status until a new one is approved.

The family is growing. IEEE 1815.2-2025, approved in November 2025 and published on 5 February 2026, defines a DNP3 profile for distributed energy resources. It maps selected IEC 61850-7-420 data objects to a fixed list of DNP3 points and covers functions from IEEE 1547-2018 and related standards, work the DNP Users Group carried out jointly with the MESA Standards Alliance.

Security has its own track. IEEE 1815-2012 includes Secure Authentication version 5 for checking critical requests. The DNP Users Group describes Secure Authentication version 6 as an implementation of IEC 62351-5, covered in our [IEC 62351](https://quantlix.com/en/standards/iec-62351/) guide, and its recent work includes a DNP3 Security Layer and an Authorization Management Protocol. Where these systems belong to the North American bulk electric system, [NERC CIP](https://quantlix.com/en/standards/nerc-cip/) requirements apply as well.

### How it shows up in software projects

- **Point maps as contracts.** Each link has a documented point list with indexes, types, scaling, deadbands and event classes, agreed with the utility and kept under version control.
- **Time and quality handling.** Events carry timestamps and quality flags, and the software keeps both, copes with events that arrive late and records where each timestamp came from.
- **Integrity after reconnects.** After a link drops, the master runs an integrity poll before trusting the data again, and the software marks the gap.
- **Direction of control.** Monitoring and control are separated, and operations such as select-before-operate are enabled only on points the utility has approved.
- **Testing against profiles.** Simulators built from the device profile let you test mappings before anything connects to live outstations.

### How we work with DNP3

We build the software that sits around DNP3 links: gateways and adapters that bring outstation data into historians, analytics and operational systems, point map tooling, and test harnesses that exercise a mapping before it touches the field. This work often goes hand in hand with modernizing older SCADA interfaces while keeping the protocol the utility already runs.

Device conformance comes from the DNP Users Group program and the device maker, and the utility decides which links may carry controls. We design within those decisions. Our Utilities and Infrastructure practice is led by [Dr. Abdel-Hadi Hor](https://quantlix.com/en/about/leadership/abdel-hadi-hor/), and you can find more about this field on our [energy and utilities](https://quantlix.com/en/industries/energy-and-utilities/) page.

## Where it applies

Industries where this standard often shapes the work.

- ### [Energy & Utilities](https://quantlix.com/en/industries/energy-and-utilities/)

  Renewable energy, smart grids and energy storage systems

## Related standards

[All standards](https://quantlix.com/en/standards/)

- IEC 60870-5-104

  ### [Telecontrol over TCP/IP networks](https://quantlix.com/en/standards/iec-60870-5-104/)

  IEC 60870-5-104 is the international telecontrol standard that carries IEC 60870-5-101 messages over TCP/IP, so control centers can monitor and control substations and other remote sites over IP networks.
- IEC 61850

  ### [Power utility automation and substations](https://quantlix.com/en/standards/iec-61850/)

  IEC 61850 is the international standard series for communication in power utility automation, defining device data models, the SCL configuration language and fast messaging for substations and other grid assets.
- IEC 62351

  ### [Security for power system protocols](https://quantlix.com/en/standards/iec-62351/)

  IEC 62351 is the IEC series that adds authentication, encryption, access control and key management to the communication protocols that run power systems, such as IEC 61850, IEC 60870-5 and DNP3.
- NERC CIP

  ### [Cyber security for the bulk power system](https://quantlix.com/en/standards/nerc-cip/)

  NERC CIP is the family of mandatory reliability standards that protect the cyber systems and critical facilities of the North American bulk power system, from system categorization to supply chain risk.

## Services that support this work

The services we usually bring to projects that involve this standard.

[View all services](https://quantlix.com/en/services/)

### [IoT and edge computing](https://quantlix.com/en/services/iot-edge-computing/)

Connect machines, sensors and business software with assessed IoT and edge integrations. Define data meaning, connectivity, permitted actions and recovery.

### [Enterprise applications](https://quantlix.com/en/services/enterprise-applications/)

Quantlix designs and builds enterprise applications for internal workflows, business rules and system integration, with clear access controls and maintainable architecture.

### [Legacy modernization](https://quantlix.com/en/services/legacy-modernization/)

Quantlix modernizes existing systems through targeted changes, integration and staged migration, preserving essential business behavior while addressing technical constraints.

## Questions, answered

What teams usually ask us about this standard.

**Is DNP3 the same as IEEE 1815?**

Yes. DNP3 was first adopted as IEEE Std 1815 in 2010 and revised as IEEE 1815-2012. The DNP Users Group still owns and maintains the protocol and feeds its refinements into the next IEEE update.

**Is IEEE 1815-2012 still valid if it is inactive?**

It is still the latest published edition. IEEE has listed it as Inactive-Reserved since 30 March 2023, and revision project P1815 is active. Specifications should cite the 2012 edition with that status until a revised edition is approved.

**What is the difference between DNP3 and IEC 60870-5-104?**

Both carry SCADA data between control centers and field devices, and DNP3 grew from the same IEC 60870-5 groundwork. DNP3 is maintained by the DNP Users Group and IEEE, while IEC 60870-5-104 is an IEC companion standard that carries IEC 60870-5-101 messages over TCP/IP.

**How is DNP3 secured?**

IEEE 1815-2012 includes Secure Authentication version 5, which challenges critical requests before they are acted on. The DNP Users Group describes its newer version 6 as an implementation of IEC 62351-5. Network segmentation and monitoring still matter on every link.

**Can a DNP3 device be certified?**

Yes, at device level. The DNP Users Group runs a conformance certification program, reviews test results against its published test procedures and posts the certificates publicly.

**Which port does DNP3 use over IP?**

IANA registers port 20000 for DNP over both TCP and UDP. Utilities can configure other ports, so confirm the setting for each link.

## Official sources

Read the official text before relying on any detail. What applies to you depends on your role, your location and the version in force.

- [IEEE 1815-2012 on IEEE SA](https://standards.ieee.org/ieee/1815/5414/)
- [DNP Users Group](https://www.dnp.org/)
- [Overview of DNP3 (DNP Users Group)](https://www.dnp.org/About/Overview-of-DNP3-Protocol)
- [IEEE 1815.2-2025 DER profile on IEEE SA](https://standards.ieee.org/ieee/1815.2/7731/)

These guides explain each standard in plain terms. They are not legal advice, and they do not state that any product or organization conforms to a standard.

## Planning software around this standard?

Tell us which systems are involved and what you need to show. We will help you build the requirements in from the start.

[Discuss your project](https://quantlix.com/en/contact/)